local_fire_department

Fire Inspection & DKV — Free Guide and Checklists

Everything you need to know about the operations, control, and maintenance plan for fire safety in Danish buildings. Legal requirements, frequencies, and complete checklists.

What is DKV?

DKV stands for Drift, Kontrol og Vedligehold (Operations, Control, and Maintenance). It is the legal framework for fire safety in buildings throughout their lifetime. The requirements are based on BR18 sections 137-158, Chapter 7, and cover all fire protection installations and passive fire safety measures in a building.

gavel Responsibility

The building owner bears full responsibility for DKV. Responsibility can be delegated to an operations manager, but it cannot be transferred — the owner is always liable.

Consequences of non-compliance

warning Risks of inadequate DKV

  • Enforcement orders: 38% of inspected buildings receive enforcement orders during fire inspections.
  • Prohibition: The building can be shut down with immediate effect.
  • Fines/imprisonment: Up to 4 months imprisonment (aggravating circumstances: up to 2 years).
  • Insurance: Insurance companies may reduce or deny coverage.

Inspection Frequencies

Overview of mandatory inspection frequencies for fire protection installations per BR18 and relevant standards.

System / Installation Self-inspection External service Accredited
ABA (fire alarm) Monthly Annually Annually
Sprinkler (AVS) Weekly Annually Annually
Smoke ventilation (ABV) Monthly Annually Annually
Fire door closing (ABDL) Quarterly Every 2 years
Warning system Quarterly Every 2 years Every 4 years
Smoke alarm system Quarterly
Emergency exit lighting Monthly Every 2 years Every 4 years
Fire hose reels Semi-annually (cat. 6 only) Annually
Fire blankets Annually
Fire doors (without ABDL) Annually
Fire dampers Annually Annually
Passive fire protection Annually

Sample Checklist — ABA System (Fire Alarm)

Excerpt from Normo's bilingual checklist for self-inspection of ABA systems. The complete checklist with all checkpoints is available in the PDF guide.

Checkpoint (DK) Checkpoint (EN) Type
Centralapparat viser normal drift Control panel shows normal operation Fixed
Alle systemkomponenter tilsluttet All system components connected Fixed
Kun aftalte enheder frakoblet Only agreed units disconnected Fixed
Langvarige fejlmeddelelser under udbedring Long-term error messages being addressed Fixed
Forsikringsselskab informeret om fejl Insurance company informed about faults Custom
Brandvæsenets adgang til ABA-central matcher aftale Fire service access matches agreement Fixed
Kontroller om lase er skiftet siden sidst Check if locks changed since last inspection Fixed

Download Complete Guide

10 pages with legal requirements, 12 inspection frequencies, and 6 complete checklists.

download Download PDF

Use the checklists digitally in Normo

Stop the manual paperwork. With Normo, you get all fire inspection checklists digitally in the mobile app.

  • check Automatic scheduling of all inspection frequencies
  • check Photo documentation directly from the mobile app
  • check PDF reports ready for fire authorities and insurance
rocket_launch Get started